Permit Details

Status:
Final
Type:
COMMERCIAL ALTERATION
Address NEW:
2475 N HASKELL DR
Apply Date:
11/10/2008
Applicant:
UNITED FIRE EQUIPMENT CO,*C,*P
Description:
ADD 48 HORN STROBES
Contractors:
  • UNITED FIRE EQUIPMENT CO,*C,*P

Outstanding Activity Conditions

Permit Number - T08BU01984
Permit Status: Final
Permit Description: ADD 48 HORN STROBES
Total Outstanding Activity Conditions - 1
Date Name
11/10/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T08BU01984
Permit Description: ADD 48 HORN STROBES
Total Completed Inspections - 2
Date Description Inspector Results Comments
12/16/2008 FIRE - ALARM FINAL CSCHULTZ Approved Power off using battery mode:
No signal for low battery - on both panels
No alarm on 1st floor water flow
No singal for missing horn
No outside alarm bell when testing flow switches.

A/C on
Same as above
Set smoke alarms off no alarms sounded.
No alarm bells on water flows.
02/19/2009 PERMIT FINALED CSCHULTZ Approved