Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T08BU01984
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/19/2009 | FIRE - ALARM FINAL | Approved | ||
02/18/2009 | FIRE - ALARM FINAL | Denied | ON 24HR STANDBY TEST 2:00PM RUN TEST FOR 5MINS ON 2/19/2009 AT 2:00PM | |
01/27/2009 | FIRE - ALARM FINAL | Denied | Batteries on burglary/fire panel died during test. Will need to do 24 hour stand-by on batteries then 5 min. full run time for final test. | |
12/16/2008 | FIRE - ALARM FINAL | Denied | Power off using battery mode: No signal for low battery - on both panels No alarm on 1st floor water flow No singal for missing horn No outside alarm bell when testing flow switches. A/C on Same as above Set smoke alarms off no alarms sounded. No alarm bells on water flows. |
|
11/18/2008 | FIRE - ALARM FINAL | Not ready for Inspection | FIRE ALARM PANELS AND NAC'S SHALL BE ON A DEDICATED CIRCUIT LABEL ALARM PANELS AND NAC'S WITH CIRCUIT NUMBER AND LOCATION OF BREAKER PANEL. LABEL ALL BATTERIES WITH INSTALLATION DATE INSTALL SMOKE DETECTOR OVER FIRE ALARM PANELS |