Permit: T08BU01984

Parcel: 111084910


Addresses:

2475 N HASKELL DR

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
02/19/2009 FIRE - ALARM FINAL Approved
02/18/2009 FIRE - ALARM FINAL Denied ON 24HR STANDBY TEST 2:00PM RUN TEST FOR 5MINS ON 2/19/2009 AT 2:00PM
01/27/2009 FIRE - ALARM FINAL Denied Batteries on burglary/fire panel died during test. Will need to do 24 hour stand-by on batteries then 5 min. full run time for final test.
12/16/2008 FIRE - ALARM FINAL Denied Power off using battery mode:
No signal for low battery - on both panels
No alarm on 1st floor water flow
No singal for missing horn
No outside alarm bell when testing flow switches.

A/C on
Same as above
Set smoke alarms off no alarms sounded.
No alarm bells on water flows.
11/18/2008 FIRE - ALARM FINAL Not ready for Inspection FIRE ALARM PANELS AND NAC'S SHALL BE ON A DEDICATED CIRCUIT
LABEL ALARM PANELS AND NAC'S WITH CIRCUIT NUMBER AND LOCATION OF BREAKER PANEL.
LABEL ALL BATTERIES WITH INSTALLATION DATE
INSTALL SMOKE DETECTOR OVER FIRE ALARM PANELS