Permit Details

Status:
Closed
Type:
COMMERCIAL OTHER
Apply Date:
08/01/2008
Applicant:
APCON CONSTRUCTION CO INC
Description:
Relocate 10 and add 7 fire sprinklers
Contractors:
  • APCON CONSTRUCTION CO INC

Outstanding Activity Conditions

Permit Number - T08BU01401
Permit Status: Closed
Permit Description: Relocate 10 and add 7 fire sprinklers
Total Outstanding Activity Conditions - 1
Date Name
08/01/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Closed
Permit Number: T08BU01401
Permit Description: Relocate 10 and add 7 fire sprinklers
Total Completed Inspections - 1
Date Description Inspector Results Comments
08/10/2010 FIRE SPKLR - FINAL CSCHULTZ Approved C of O okay for use of suite 101 only do not use any other part of building until all new plans for building, sprinkler, fire alarm and any other required plans and permits are approved and all construction is finished.
According to plans sprinklers are installed per approved plans. Did received a sprinkler report from simplex Grinnell showing deficiencies need to correct sprinkler coverage on the 2nd floor and 3rd, and 4th floor. Will need flow switches on a monitoring system. New electric motor installed for fire pump with out permits by Grinnell but tests show pump is fully operational.

Documents

File Name Document Type  
SPRINKLER_001.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW