Permit: T08BU01401

Parcel: 117130410

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T08BU01401

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/10/2010 FIRE SPKLR - FINAL Approved C of O okay for use of suite 101 only do not use any other part of building until all new plans for building, sprinkler, fire alarm and any other required plans and permits are approved and all construction is finished.
According to plans sprinklers are installed per approved plans. Did received a sprinkler report from simplex Grinnell showing deficiencies need to correct sprinkler coverage on the 2nd floor and 3rd, and 4th floor. Will need flow switches on a monitoring system. New electric motor installed for fire pump with out permits by Grinnell but tests show pump is fully operational.