Description:
KITCHEN HOOD SYSTEM
Contractors:
  • R C I SYSTEMS INC ,

Permit Reviews

Permit Number - T08BU00802
Permit Status: Expired
Permit Description: KITCHEN HOOD SYSTEM
Start Date Submittal Complete Date Status  
04/25/2008 MECHANICAL 04/25/2008 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T08BU00802
Permit Status: Expired
Permit Description: KITCHEN HOOD SYSTEM
Total Outstanding Activity Conditions - 1
Date Name
04/25/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T08BU00802
Permite Description: KITCHEN HOOD SYSTEM
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
FIRE - KITCHEN EXH HOOD FINAL N/A Not Inspected
06/11/2008 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. LARGE HOOD GREASE DUCT DOES NOT HAVE MIN. 18" CLEARANCE TO COMBUSTIBLES
2. PROVIDE 2 LAYERS OF FIRE WRAP ON ENTIRE GREASE DUCT
3. SMALL HOOD GREASE DUCT NOT TYPE 1 & DOES NOT HAVE ADEQUATE CLEARANCE TO COMBUSTIBLES
4. BOTH EXHAUST FANS DO NOT APPEAR TO BE TYPE I RATED
5. BELTS & PULLEYS NEED COVERS OVER THEM
6. IF FANS NEED TO BE REPLACED, PROVIDE AN ENGINEERED DRAWING APPROVED BY THE CITY OF TUCSON
7. PROVIDE A MECHANICAL PERMIT & SCHEDULE AN INSPECTION WHEN WORK IS COMPLETE
8. MAKE UP AIR NOT INTERLOCKED WITH EXHAUST EQUIPMENT
9. BOTH HOODS ARE OK FOR TYPE I REQUIREMENTS