Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T08BU00802
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/11/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. LARGE HOOD GREASE DUCT DOES NOT HAVE MIN. 18" CLEARANCE TO COMBUSTIBLES 2. PROVIDE 2 LAYERS OF FIRE WRAP ON ENTIRE GREASE DUCT 3. SMALL HOOD GREASE DUCT NOT TYPE 1 & DOES NOT HAVE ADEQUATE CLEARANCE TO COMBUSTIBLES 4. BOTH EXHAUST FANS DO NOT APPEAR TO BE TYPE I RATED 5. BELTS & PULLEYS NEED COVERS OVER THEM 6. IF FANS NEED TO BE REPLACED, PROVIDE AN ENGINEERED DRAWING APPROVED BY THE CITY OF TUCSON 7. PROVIDE A MECHANICAL PERMIT & SCHEDULE AN INSPECTION WHEN WORK IS COMPLETE 8. MAKE UP AIR NOT INTERLOCKED WITH EXHAUST EQUIPMENT 9. BOTH HOODS ARE OK FOR TYPE I REQUIREMENTS |
|
05/30/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO ONE ON SITE |