Permit: T08BU00206
Permit Details
Apply Date:
02/04/2008
Applicant:
RICHARD ANDERSEN
Description:
FIRE SUPPRESSION HOOD
Contractors:
- S & M FIRE SYSTEMS INC/IDEAL FIRE **C**
Permit Reviews
Permit Number - T08BU00206
Permit Status: Expired
Permit Description: FIRE SUPPRESSION HOOD
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
02/04/2008 | MECHANICAL | 02/04/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T08BU00206
Permit Status: Expired
Permit Description: FIRE SUPPRESSION HOOD
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
02/04/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T08BU00206
Permite Description: FIRE SUPPRESSION HOOD
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/08/2008 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* - 3/8" ID GAS FLEX TO THE GAS RANGE IS TOO LONG AND NOT ADEQUATE DIAMETER. USE 3/4 I.D - SEAL OPENING AROUND GAS PIPE - HOODS, GREASE DUCTS AND FANS ARE OK - REPLACE HVAC RATED DUCT ON ROOF WITH 16GA STEEL WELDED ELBOW - PROVIDE TYPE 1 RATED CLEANOUTS IN DUCTS ON ROOF - CANNOT SEE DUCTS INSIDE SHAFT - 2 STORY BLDG. - INTERLOCK EXHAUST FANS WITH MAKE UP AIR UNIT - OK TO INSTALL FIRE SUPPRESSION SYSTEM |