Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Apply Date:
02/04/2008
Applicant:
RICHARD ANDERSEN
Description:
FIRE SUPPRESSION HOOD
Contractors:
  • S & M FIRE SYSTEMS INC/IDEAL FIRE **C**

Permit Reviews

Permit Number - T08BU00206
Permit Status: Expired
Permit Description: FIRE SUPPRESSION HOOD
Start Date Submittal Complete Date Status  
02/04/2008 MECHANICAL 02/04/2008 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T08BU00206
Permit Status: Expired
Permit Description: FIRE SUPPRESSION HOOD
Total Outstanding Activity Conditions - 1
Date Name
02/04/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T08BU00206
Permite Description: FIRE SUPPRESSION HOOD
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
02/08/2008 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
- 3/8" ID GAS FLEX TO THE GAS RANGE IS TOO LONG AND NOT ADEQUATE DIAMETER. USE 3/4 I.D
- SEAL OPENING AROUND GAS PIPE
- HOODS, GREASE DUCTS AND FANS ARE OK
- REPLACE HVAC RATED DUCT ON ROOF WITH 16GA STEEL WELDED ELBOW
- PROVIDE TYPE 1 RATED CLEANOUTS IN DUCTS ON ROOF
- CANNOT SEE DUCTS INSIDE SHAFT - 2 STORY BLDG.
- INTERLOCK EXHAUST FANS WITH MAKE UP AIR UNIT
- OK TO INSTALL FIRE SUPPRESSION SYSTEM