Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T08BU00206
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/08/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - 3/8" ID GAS FLEX TO THE GAS RANGE IS TOO LONG AND NOT ADEQUATE DIAMETER. USE 3/4 I.D - SEAL OPENING AROUND GAS PIPE - HOODS, GREASE DUCTS AND FANS ARE OK - REPLACE HVAC RATED DUCT ON ROOF WITH 16GA STEEL WELDED ELBOW - PROVIDE TYPE 1 RATED CLEANOUTS IN DUCTS ON ROOF - CANNOT SEE DUCTS INSIDE SHAFT - 2 STORY BLDG. - INTERLOCK EXHAUST FANS WITH MAKE UP AIR UNIT - OK TO INSTALL FIRE SUPPRESSION SYSTEM |