Permit: T08BU00206

Parcel: 12212341D


Addresses:

1661 N SWAN RD #120


Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Permit Number - T08BU00206

Inspection Description - MECHANICAL - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
02/08/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- 3/8" ID GAS FLEX TO THE GAS RANGE IS TOO LONG AND NOT ADEQUATE DIAMETER. USE 3/4 I.D
- SEAL OPENING AROUND GAS PIPE
- HOODS, GREASE DUCTS AND FANS ARE OK
- REPLACE HVAC RATED DUCT ON ROOF WITH 16GA STEEL WELDED ELBOW
- PROVIDE TYPE 1 RATED CLEANOUTS IN DUCTS ON ROOF
- CANNOT SEE DUCTS INSIDE SHAFT - 2 STORY BLDG.
- INTERLOCK EXHAUST FANS WITH MAKE UP AIR UNIT
- OK TO INSTALL FIRE SUPPRESSION SYSTEM