Permit: T07OT01841
Permit Details
Apply Date:
08/15/2007
Applicant:
ADDISIGNS INC
Description:
13520
Contractors:
- ADDISIGNS INC
Outstanding Inspections
Permit Status: Expired
Permit Number: T07OT01841
Permite Description: 13520
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/18/2007 | SIGN SHOP | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROPERLY INSTALL LOCKNUTS 2. PROTECT CABLES AT PASS THRU FROM SHARP METAL EDGES 3. BOND LETTERS 600.7 4. SUPPORT MC CABLE AS PER CODE 330.30 - 12" FROM BOXES 5. CLEAN EXCESS TRASH AND OLD SIGN PARTS FROM SOFFIT 6. NEED SERVICE LIGHT 210.70 7. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR 8. MONUMENT CHANGE OF COPY IS IN AN UNFINISH/NON-APPROVED SIGN |
| 09/18/2007 | SIGN ELECTRIC | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
Completed Inspections
Permit Status: Expired
Permit Number: T07OT01841
Permit Description: 13520
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2007 | SIGN SITE REVIEW | JYBARRA | Approved | |
| 09/18/2007 | SIGN INSPECTION | JYBARRA | Approved | DF SIGN CHANGE OF COPY NOT COMPLETE TO DATE; ALL OTHERS ARE OK |