Permit: T07OT01841

Parcel: 10408053L

Inspection Status: Denied

Inspection History: SIGN SHOP

Date Description Inspector Results Comments
09/18/2007 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROPERLY INSTALL LOCKNUTS
2. PROTECT CABLES AT PASS THRU FROM SHARP METAL EDGES
3. BOND LETTERS 600.7
4. SUPPORT MC CABLE AS PER CODE 330.30 - 12" FROM BOXES
5. CLEAN EXCESS TRASH AND OLD SIGN PARTS FROM SOFFIT
6. NEED SERVICE LIGHT 210.70
7. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR
8. MONUMENT CHANGE OF COPY IS IN AN UNFINISH/NON-APPROVED SIGN