Permit: T07OT00942
Permit Details
Apply Date:
04/20/2007
Applicant:
ROYAL SIGN CO INC , *C
Description:
12990
Contractors:
- ROYAL SIGN CO INC , *C
Outstanding Inspections
Permit Status: Expired
Permit Number: T07OT00942
Permite Description: 12990
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/02/2007 | SIGN SHOP | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
| 05/02/2007 | SIGN ELECTRIC | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ISOLATE POWER TO SWITCH 2. A MARKING LABEL IS NEEDED 600.4 3. SUPPORT JUNCTION BOXES & CONDUIT ACROSS ROOF 4. GROUND JUNCTION BOXES 5. TIGHTEN LOOSE FITTINGS 6. COVER PLATE IS MISSING FOR A JUNCTION BOX AND CONDUCTORS ARE DETERIORATED -- NEEDS TO BE REPLACED 7. SUPPORT SEAL TITE AT SIGNS |
Completed Inspections
Permit Status: Expired
Permit Number: T07OT00942
Permit Description: 12990
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/23/2007 | SIGN SITE REVIEW | JYBARRA | Approved | IVRS - Inspection :* |
| 05/02/2007 | SIGN INSPECTION | JYBARRA | Approved | IVRS - Inspection :* |