Inspection History Details
Inspection Status: Denied
Inspection History: SIGN ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/02/2007 | SIGN ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ISOLATE POWER TO SWITCH 2. A MARKING LABEL IS NEEDED 600.4 3. SUPPORT JUNCTION BOXES & CONDUIT ACROSS ROOF 4. GROUND JUNCTION BOXES 5. TIGHTEN LOOSE FITTINGS 6. COVER PLATE IS MISSING FOR A JUNCTION BOX AND CONDUCTORS ARE DETERIORATED -- NEEDS TO BE REPLACED 7. SUPPORT SEAL TITE AT SIGNS |