Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
MOBILE HOME: MH PARK
Address NEW:
1070 E GINTER RD #01
Apply Date:
02/02/2007
Applicant:
MARIA PLASENCIA
Description:
MH SET UP

Permit Reviews

Permit Number - T07MH00018
Permit Status: Expired
Permit Description: MH SET UP
Start Date Submittal Complete Date Status  
02/02/2007 MOBILE HOME 02/02/2007 ACTIVE Review Details

Outstanding Activity Conditions

Permit Number - T07MH00018
Permit Status: Expired
Permit Description: MH SET UP
Total Outstanding Activity Conditions - 1
Date Name
02/02/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07MH00018
Permite Description: MH SET UP
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
ELECTRIC - FINAL N/A Not Inspected
03/02/2007 ELECTRIC - RECONNECT N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ROMEX IN EAST BATHROOM MUST BE RUN THRU WOOD STUD, NOT ON SURFACE, INSTALL APPROVED BOX FOR LIGHT BAR FIXTURE.
2. INSTALL SMOKE DETECTORS IN BEDROOMS.
3. FEEDER FOR PANEL TOO SMALL FOR 100 AMP CIRCUIT BREAKER - SHOULD BE #2 COPPER OR 1/0 ALUM
4. CONDUIT MUST BE 18" MIN, DEPTH,
5. INSTALL W/P BOX & COVER FOR COOLER WIRING ON ROOF.