Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2007 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ROMEX IN EAST BATHROOM MUST BE RUN THRU WOOD STUD, NOT ON SURFACE, INSTALL APPROVED BOX FOR LIGHT BAR FIXTURE. 2. INSTALL SMOKE DETECTORS IN BEDROOMS. 3. FEEDER FOR PANEL TOO SMALL FOR 100 AMP CIRCUIT BREAKER - SHOULD BE #2 COPPER OR 1/0 ALUM 4. CONDUIT MUST BE 18" MIN, DEPTH, 5. INSTALL W/P BOX & COVER FOR COOLER WIRING ON ROOF. |