Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T07MH00018

Parcel: 14024057C

Inspection Status: Denied

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
03/02/2007 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ROMEX IN EAST BATHROOM MUST BE RUN THRU WOOD STUD, NOT ON SURFACE, INSTALL APPROVED BOX FOR LIGHT BAR FIXTURE.
2. INSTALL SMOKE DETECTORS IN BEDROOMS.
3. FEEDER FOR PANEL TOO SMALL FOR 100 AMP CIRCUIT BREAKER - SHOULD BE #2 COPPER OR 1/0 ALUM
4. CONDUIT MUST BE 18" MIN, DEPTH,
5. INSTALL W/P BOX & COVER FOR COOLER WIRING ON ROOF.