Description:
INSTALL NEW 3 TON GAS PACK (APA)
Contractors:
  • CUMMINGS PLUMBING INC , *C

Outstanding Activity Conditions

Permit Number - T07ME00733
Permit Status: Expired
Permit Description: INSTALL NEW 3 TON GAS PACK (APA)
Total Outstanding Activity Conditions - 1
Date Name
10/31/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07ME00733
Permite Description: INSTALL NEW 3 TON GAS PACK (APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
11/07/2007 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL JOINTS ON EXTERIOR OF DUCT INCLUDING LONGITUDINAL ARE TO BE SEALED
2. UNIT NOT LEVEL
3. DISCONNECT NOT PROPERLY FASTENED TO BUILDING
4. GAS FLEX NOT RATED FOR UNIT BTU
5. UNIT OVERFUSED 35 AMP MAX
6. PROVIDE ROOF JACK AT ELEC. PENETRATIONS
7. PROVIDE ROOF JACK AT GAS PENETRATIONS
8. WAS NEW GAS PIPE PERMITTED & APPROVED
9. ALL CONDENSATE EXPOSED TO EXTERIOR IS TO BE PAINTED WITH LATEX PAINT
10. SEAL ALL SCREWS THAT PENETRATE EXTERIOR DUCT
11. CONDENSATE PIPING SUPPORT NOT TO EXCEED 5' ON PVC