Permit: T07ME00733

Parcel: 108210130


Addresses:

1441 E PROSPECT LN

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/07/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL JOINTS ON EXTERIOR OF DUCT INCLUDING LONGITUDINAL ARE TO BE SEALED
2. UNIT NOT LEVEL
3. DISCONNECT NOT PROPERLY FASTENED TO BUILDING
4. GAS FLEX NOT RATED FOR UNIT BTU
5. UNIT OVERFUSED 35 AMP MAX
6. PROVIDE ROOF JACK AT ELEC. PENETRATIONS
7. PROVIDE ROOF JACK AT GAS PENETRATIONS
8. WAS NEW GAS PIPE PERMITTED & APPROVED
9. ALL CONDENSATE EXPOSED TO EXTERIOR IS TO BE PAINTED WITH LATEX PAINT
10. SEAL ALL SCREWS THAT PENETRATE EXTERIOR DUCT
11. CONDENSATE PIPING SUPPORT NOT TO EXCEED 5' ON PVC