Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
2590 N SANTA ROSA AV
Apply Date:
08/01/2007
Applicant:
RINCON AIR COND AND HEAT,*C,*P
Description:
REPLACE: 5 TON GAS/ELECT UNIT (APA)
Contractors:
  • RINCON AIR COND AND HEAT,*C,*P

Outstanding Activity Conditions

Permit Number - T07ME00559
Permit Status: Expired
Permit Description: REPLACE: 5 TON GAS/ELECT UNIT (APA)
Total Outstanding Activity Conditions - 1
Date Name
08/01/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07ME00559
Permite Description: REPLACE: 5 TON GAS/ELECT UNIT (APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
08/16/2007 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING NO-LOX, ON ALUMINUM CONDUCTORS IN DISCONNECT
2) DISCONNECT NOT SECURED
3) PIPE OR HOLE IN ROOF NORTH OF NEW UNIT (OPEN)
4) RED WOOD SKIDS, RUNNING PARALLEL WITH RAFTERS ?
5) APPROX 75' OF GAS PIPE TO NEW UNIT FROM METER UNIT 105 CFH=75' RUN=118 CFH MAX 3/4" DIAMETER PIPE. YOU HAVE REDUCED GAS LINE FROM 1" DOWN TO 1/2" WITHOUT DEDUCTING UNIT DEMANDS, YOU ALSO HAVE 1/2" PIPE GOING INTO HOUSE FEEDING ANOTHER APPLIANCE. PLEASE LEAVE GAS DIAGRAM SHOWING LENGTH AND DEMAND, ADJUST ACCORDINGLY
5) CONDENSATE DRAINING INTO ROOF GUTTER FULL OF H20 NOT DRAINING
6) SUPPORT CONDENSATE LINE FOR CONSISTENT SLOPE
7) NEED TO VERIFY WIRE SIZE FUSING UNIT MAX 60 OVER CURRENT 44.5 CIRCUIT AMPACITY #8 AW=40 AMPS

Documents

File Name Document Type  
None DOCUMENTS VIEW