Permit: T07ME00559

Parcel: 110112680

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Permit Number - T07ME00559

Inspection Description - MECHANICAL - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
08/16/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING NO-LOX, ON ALUMINUM CONDUCTORS IN DISCONNECT
2) DISCONNECT NOT SECURED
3) PIPE OR HOLE IN ROOF NORTH OF NEW UNIT (OPEN)
4) RED WOOD SKIDS, RUNNING PARALLEL WITH RAFTERS ?
5) APPROX 75' OF GAS PIPE TO NEW UNIT FROM METER UNIT 105 CFH=75' RUN=118 CFH MAX 3/4" DIAMETER PIPE. YOU HAVE REDUCED GAS LINE FROM 1" DOWN TO 1/2" WITHOUT DEDUCTING UNIT DEMANDS, YOU ALSO HAVE 1/2" PIPE GOING INTO HOUSE FEEDING ANOTHER APPLIANCE. PLEASE LEAVE GAS DIAGRAM SHOWING LENGTH AND DEMAND, ADJUST ACCORDINGLY
5) CONDENSATE DRAINING INTO ROOF GUTTER FULL OF H20 NOT DRAINING
6) SUPPORT CONDENSATE LINE FOR CONSISTENT SLOPE
7) NEED TO VERIFY WIRE SIZE FUSING UNIT MAX 60 OVER CURRENT 44.5 CIRCUIT AMPACITY #8 AW=40 AMPS