Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T07ME00508
Permit Details
Apply Date:
07/11/2007
Applicant:
MORANDO MINI
Description:
CHANGEOUT OF TRANE 5 TON SPLIT AC/GAS ( LEIGHTON 444.4344)
Contractors:
- AMERICAN HOME MAINTENANCE INC *C
Outstanding Activity Conditions
Permit Number - T07ME00508
Permit Status: Expired
Permit Description: CHANGEOUT OF TRANE 5 TON SPLIT
AC/GAS ( LEIGHTON 444.4344)
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
07/11/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07ME00508
Permite Description: CHANGEOUT OF TRANE 5 TON SPLIT
AC/GAS ( LEIGHTON 444.4344)
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/24/2007 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. THE OUTLET OF THE P-TRAP IS HIGHER THAN THE OUTLET OF THE MAIN DRAIN. CHECK YOUR OVERFLOW SENSOR FOR CORRECT INSTALLATION, REPAIR P-TRAP AND PROVIDE MINIMUM 1/8" PER FOOT FALL ON CONDENSATE DRAIN PIPING SUPPORTED AT 4' INTERVALS. |