Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/24/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. THE OUTLET OF THE P-TRAP IS HIGHER THAN THE OUTLET OF THE MAIN DRAIN. CHECK YOUR OVERFLOW SENSOR FOR CORRECT INSTALLATION, REPAIR P-TRAP AND PROVIDE MINIMUM 1/8" PER FOOT FALL ON CONDENSATE DRAIN PIPING SUPPORTED AT 4' INTERVALS. |