Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T07ME00508
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/24/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. THE OUTLET OF THE P-TRAP IS HIGHER THAN THE OUTLET OF THE MAIN DRAIN. CHECK YOUR OVERFLOW SENSOR FOR CORRECT INSTALLATION, REPAIR P-TRAP AND PROVIDE MINIMUM 1/8" PER FOOT FALL ON CONDENSATE DRAIN PIPING SUPPORTED AT 4' INTERVALS. |