Permit: T07ME00477
Permit Details
Apply Date:
06/28/2007
Applicant:
MORANDO MINI
Description:
VIRGIN INSTALL OF TRANE 5T PAC AC/GAS ( SIERRA 207.6668)
Contractors:
- AMERICAN HOME MAINTENANCE INC *C
Outstanding Activity Conditions
Permit Number - T07ME00477
Permit Status: Final
Permit Description: VIRGIN INSTALL OF TRANE 5T PAC
AC/GAS ( SIERRA 207.6668)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 06/28/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T07ME00477
Permit Description: VIRGIN INSTALL OF TRANE 5T PAC
AC/GAS ( SIERRA 207.6668)
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/19/2007 | MECHANICAL - FINAL | MRAMBER | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1) FUSES TO SMALL 2) CONTRACTOR TO BE PRESENT ON NEXT INSPECTION TO VERIFY R-8 INSULATION IN EXTERIOR DUCT WORK 3) PROVIDE PRESSURE TEST INSPECTION ON GAS PIPING 4) BREAKERS AT SUB PANEL TO SMALL |
| 11/27/2007 | MECHANICAL - INTERMEDIATE | MRAMBER | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1) EXTERIOR DUCT IS NOT R-8, MUST PROVIDE 2" DUCT LINER OR OTHER MEANS |
| 02/02/2009 | PERMIT FINALED | BFLORES | Approved |