Permit: T07ME00477

Parcel: 138142880


Addresses:

242 W HATFIELD ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/30/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
01/28/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
01/16/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONTRACTOR DID NOT RETURN PHONE CALL THAT HE REQUESTED. 45 MIN. PASSED FROM MY CALL TO THE TIME I SHOWED UP ON SITE.
01/15/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
11/19/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FUSES TO SMALL
2) CONTRACTOR TO BE PRESENT ON NEXT INSPECTION TO VERIFY R-8 INSULATION IN EXTERIOR DUCT WORK
3) PROVIDE PRESSURE TEST INSPECTION ON GAS PIPING
4) BREAKERS AT SUB PANEL TO SMALL
07/18/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
WORK SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION PURPOSES UNTIL APPROVED IN ACCORDANCE WITH THE SECTION 109.1 IBC
PROVIDE ACCESS TO ROOF, TURN OFF A/C UNIT
MUST REQUIRE TO VERIFY CORRECT AMPERAGE ON MAIN
SWITCH DISCONNECT