Permit: T07ME00444
Permit Details
Apply Date:
06/15/2007
Applicant:
CUMMINGS PLUMBING INC , *C
Description:
REPLACE: 4 TON GAS PACK ON ROOF (APA)
Contractors:
- CUMMINGS PLUMBING INC , *C
Outstanding Activity Conditions
Permit Number - T07ME00444
Permit Status: Expired
Permit Description: REPLACE: 4 TON GAS PACK ON ROOF (APA)
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
06/15/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07ME00444
Permite Description: REPLACE: 4 TON GAS PACK ON ROOF (APA)
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/05/2007 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 3/8" I.D X 36" GAS FLEX NOT ADEQUATE FOR 100,000 BTU FURNACE 2. PAINT EXPOSED PVC W/LATEX PAINT 3. PROVIDE MIN. R8 DUCT INSULATION IN EXPOSED DUCT ON ROOF 4. PROVIDE A BUSHING IN THE ELEC. DISCONNET PROVIDE FUSES 5. PROVIDE A NEW ELEC. CIRCUITS TO THE DISCONNECT & PROVIDE A PERMIT FOR THE NEW CIRCUIT. ALSO, PROVIDE A GFI SERVICE RECEPTACLE ON THE ROOF. 6. SUPPORT & SECURE LOW VOLTAGE CONDUIT |