5417 E DOUGLAS ST
Apply Date:
06/08/2007
Applicant:
MORANDO MINI
Description:
REPLACEMENT OF TRANE 4T SPLIT AC/GAS (ARNDT 745.5462)
Contractors:
  • AMERICAN HOME MAINTENANCE INC *C

Outstanding Activity Conditions

Permit Number - T07ME00420
Permit Status: Expired
Permit Description: REPLACEMENT OF TRANE 4T SPLIT AC/GAS (ARNDT 745.5462)
Total Outstanding Activity Conditions - 1
Date Name
06/08/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07ME00420
Permite Description: REPLACEMENT OF TRANE 4T SPLIT AC/GAS (ARNDT 745.5462)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
06/19/2007 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 3/8" I.D X 18" GAS FLEX NOT ADEQUATE FOR 96,000 BTU
2. PROVIDE SUPPORT UNDER PVC PIPE ON ROOF & PAINT ALL PVC W/LATEX PAINT. PROVIDE A ROOF JACK AT ROOF PENETRATION.
3. PROVIDE A GFI RECEPTACLE ON ROOF WITH A WATERPROOF COVER.
4. REPLACE THE WHITE WIRES USED FOR THE AC UNIT TAPING THEM BLACK WILL NOT BE ACCEPTED. PROVIDE A WATERPROOF FITTING WHERE ELEC. CONDUIT CONNECTS TO TOP OF PANEL.