Permit: T07ME00420

Parcel: 128150580


Addresses:

5417 E DOUGLAS ST

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/19/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 3/8" I.D X 18" GAS FLEX NOT ADEQUATE FOR 96,000 BTU
2. PROVIDE SUPPORT UNDER PVC PIPE ON ROOF & PAINT ALL PVC W/LATEX PAINT. PROVIDE A ROOF JACK AT ROOF PENETRATION.
3. PROVIDE A GFI RECEPTACLE ON ROOF WITH A WATERPROOF COVER.
4. REPLACE THE WHITE WIRES USED FOR THE AC UNIT TAPING THEM BLACK WILL NOT BE ACCEPTED. PROVIDE A WATERPROOF FITTING WHERE ELEC. CONDUIT CONNECTS TO TOP OF PANEL.