REPLACEMENT OF TRANE 3T SPLIT AC/GAS ( OSTERMAN 531.0865)
Contractors:
  • AMERICAN HOME MAINTENANCE INC *C

Outstanding Activity Conditions

Permit Number - T07ME00364
Permit Status: Expired
Permit Description: REPLACEMENT OF TRANE 3T SPLIT AC/GAS ( OSTERMAN 531.0865)
Total Outstanding Activity Conditions - 1
Date Name
05/24/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07ME00364
Permite Description: REPLACEMENT OF TRANE 3T SPLIT AC/GAS ( OSTERMAN 531.0865)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
06/05/2007 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RELOCATE GAS LINE FROM BLOCKING SERVICE PANEL.
2. PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET.
3. PROVIDE A PERMIT FOR NEW WATER HEATER
4. INSULATE EXPOSED SHEETMETAL DUCT ON TOP OF EVAP. COIL
5. PROVIDE A SEDIMENT TRAP IN GAS LINE TO FURNACE & WATER HEATER
6. PROPERLY IDENTIFY THE WHITE CONDUCTORS USED IN THE DISCONNECT & CIRCUIT PANEL. CLAMP ELEC. CONDUIT TO BLOCKING ON ROOF.
7. PROVIDE PROPER DESCRIPTION OF WORK. ADD NEW ELEC. CIRCUIT AND NEW A/C TO PERMIT
8. DO NOT CUT THE PLUG OFF OF THE CONDENSATE PUMP
FUSE STAT NOT REQUIRED AND CAN BE CHANGED TO A RECEPTACLE.
9. PROVIDE A DOUBLE WALL VENT W/APPROVED CAP
10. PROVIDE A SERVICE RECEPTACLE ON ROOF.