Permit: T07ME00364

Parcel: 126070470


Addresses:

3932 E POE ST

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/05/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RELOCATE GAS LINE FROM BLOCKING SERVICE PANEL.
2. PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET.
3. PROVIDE A PERMIT FOR NEW WATER HEATER
4. INSULATE EXPOSED SHEETMETAL DUCT ON TOP OF EVAP. COIL
5. PROVIDE A SEDIMENT TRAP IN GAS LINE TO FURNACE & WATER HEATER
6. PROPERLY IDENTIFY THE WHITE CONDUCTORS USED IN THE DISCONNECT & CIRCUIT PANEL. CLAMP ELEC. CONDUIT TO BLOCKING ON ROOF.
7. PROVIDE PROPER DESCRIPTION OF WORK. ADD NEW ELEC. CIRCUIT AND NEW A/C TO PERMIT
8. DO NOT CUT THE PLUG OFF OF THE CONDENSATE PUMP
FUSE STAT NOT REQUIRED AND CAN BE CHANGED TO A RECEPTACLE.
9. PROVIDE A DOUBLE WALL VENT W/APPROVED CAP
10. PROVIDE A SERVICE RECEPTACLE ON ROOF.