Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RELOCATE GAS LINE FROM BLOCKING SERVICE PANEL. 2. PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET. 3. PROVIDE A PERMIT FOR NEW WATER HEATER 4. INSULATE EXPOSED SHEETMETAL DUCT ON TOP OF EVAP. COIL 5. PROVIDE A SEDIMENT TRAP IN GAS LINE TO FURNACE & WATER HEATER 6. PROPERLY IDENTIFY THE WHITE CONDUCTORS USED IN THE DISCONNECT & CIRCUIT PANEL. CLAMP ELEC. CONDUIT TO BLOCKING ON ROOF. 7. PROVIDE PROPER DESCRIPTION OF WORK. ADD NEW ELEC. CIRCUIT AND NEW A/C TO PERMIT 8. DO NOT CUT THE PLUG OFF OF THE CONDENSATE PUMP FUSE STAT NOT REQUIRED AND CAN BE CHANGED TO A RECEPTACLE. 9. PROVIDE A DOUBLE WALL VENT W/APPROVED CAP 10. PROVIDE A SERVICE RECEPTACLE ON ROOF. |