Permit: T07ME00341
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
3003 W BROADWAY BL #0085
Address NEW:
3003 W BROADWAY BL #0085
Apply Date:
05/16/2007
Applicant:
MORANDO MINI
Description:
REPLACEMENT OF TRANE 3TON SPLIT AC/GAS ( GAY 791.3357)
Contractors:
- AMERICAN HOME MAINTENANCE INC *C
Outstanding Activity Conditions
Permit Number - T07ME00341
Permit Status: Expired
Permit Description: REPLACEMENT OF TRANE 3TON
SPLIT AC/GAS ( GAY 791.3357)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/16/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07ME00341
Permite Description: REPLACEMENT OF TRANE 3TON
SPLIT AC/GAS ( GAY 791.3357)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/24/2007 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MAX. FUSE SIZE 30 AMPS, NOT 35 2. DO NOT USE WHITE CONDUCTOR A HOT POWER LEAD WIRE INTO UNIT. 3. PROTECT CONTROL WIRING AT CONDENSOR 4. THIS JOB NEEDS TO HAVE AN ELECTRICAL PERMIT 5. REFRIGERANT COPPER AT FURNACE SIDE WALL SEPARATE/ISOLATE COPPER SUCTION LINE FROM STEEL FURNACE CASING. COMPLETE INSULATING SUCTION LINE. 6. LIMIT GAS FLEX TO 18" IN LENGTH SEAL CASING AROUND LINES AT PLENIUM. 7. WHERE IS CONDENSATE DRAIN TERMINATING? |