Permit: T07ME00341

Parcel: 116270060

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/24/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MAX. FUSE SIZE 30 AMPS, NOT 35
2. DO NOT USE WHITE CONDUCTOR A HOT POWER LEAD WIRE INTO UNIT.
3. PROTECT CONTROL WIRING AT CONDENSOR
4. THIS JOB NEEDS TO HAVE AN ELECTRICAL PERMIT
5. REFRIGERANT COPPER AT FURNACE SIDE WALL
SEPARATE/ISOLATE COPPER SUCTION LINE FROM STEEL FURNACE CASING. COMPLETE INSULATING SUCTION LINE.
6. LIMIT GAS FLEX TO 18" IN LENGTH SEAL CASING AROUND LINES AT PLENIUM.
7. WHERE IS CONDENSATE DRAIN TERMINATING?