Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/24/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MAX. FUSE SIZE 30 AMPS, NOT 35 2. DO NOT USE WHITE CONDUCTOR A HOT POWER LEAD WIRE INTO UNIT. 3. PROTECT CONTROL WIRING AT CONDENSOR 4. THIS JOB NEEDS TO HAVE AN ELECTRICAL PERMIT 5. REFRIGERANT COPPER AT FURNACE SIDE WALL SEPARATE/ISOLATE COPPER SUCTION LINE FROM STEEL FURNACE CASING. COMPLETE INSULATING SUCTION LINE. 6. LIMIT GAS FLEX TO 18" IN LENGTH SEAL CASING AROUND LINES AT PLENIUM. 7. WHERE IS CONDENSATE DRAIN TERMINATING? |