Permit: T07ME00039
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
2111 E FLORENCE DR
Address NEW:
2111 E FLORENCE DR
Apply Date:
01/24/2007
Applicant:
PUEBLO HEATING & COOLING INC *C
Description:
REPLACE: 5 TON SPLIT SYSTEM (APA)
Contractors:
- PUEBLO HEATING & COOLING INC *C
Outstanding Activity Conditions
Permit Number - T07ME00039
Permit Status: Expired
Permit Description: REPLACE: 5 TON SPLIT SYSTEM (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 01/24/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07ME00039
Permite Description: REPLACE: 5 TON SPLIT SYSTEM (APA)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/23/2007 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 3/8" I.D X 2' GAS FLEX NOT ADEQUATE FOR 100,000 BTU FURNACE. 2. USE THE PROPER REDUCER WHERE VENT CONNECTOR CONNECTS TO THE DOUBLE WALL VENT PIPE. 3. CONNECT THE OVERFLOW SENSOR ON CONDENSATE PUMP 4. DO NOT USE WHITE WIRE FOR POWER. TAPE ALL ENDS WITH BLACK TAPE. |