Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/23/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 3/8" I.D X 2' GAS FLEX NOT ADEQUATE FOR 100,000 BTU FURNACE. 2. USE THE PROPER REDUCER WHERE VENT CONNECTOR CONNECTS TO THE DOUBLE WALL VENT PIPE. 3. CONNECT THE OVERFLOW SENSOR ON CONDENSATE PUMP 4. DO NOT USE WHITE WIRE FOR POWER. TAPE ALL ENDS WITH BLACK TAPE. |