Permit: T07ME00039

Parcel: 112051810


Addresses:

2111 E FLORENCE DR

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/23/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 3/8" I.D X 2' GAS FLEX NOT ADEQUATE FOR 100,000 BTU FURNACE.
2. USE THE PROPER REDUCER WHERE VENT CONNECTOR CONNECTS TO THE DOUBLE WALL VENT PIPE.
3. CONNECT THE OVERFLOW SENSOR ON CONDENSATE PUMP
4. DO NOT USE WHITE WIRE FOR POWER. TAPE ALL ENDS WITH BLACK TAPE.