Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
5618 E 24TH ST
Address NEW:
5618 E 24TH ST
Apply Date:
12/27/2007
Applicant:
MELISSA A HOLMES
Description:
ELECTRIC:REPAIR & REPLACE 100A SERVICE LIKE FOR LIKE

Permit Reviews

Permit Number - T07EL02231
Permit Status: Expired
Permit Description: ELECTRIC:REPAIR & REPLACE 100A SERVICE LIKE FOR LIKE
Start Date Submittal Complete Date Status  
12/27/2007 ELECTRICAL 12/27/2007 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T07EL02231
Permit Status: Expired
Permit Description: ELECTRIC:REPAIR & REPLACE 100A SERVICE LIKE FOR LIKE
Total Outstanding Activity Conditions - 1
Date Name
12/27/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07EL02231
Permite Description: ELECTRIC:REPAIR & REPLACE 100A SERVICE LIKE FOR LIKE
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
12/28/2007 ELECTRIC - SERVICE UPGRADE N/A Not ready for Inspection IVRS - Inspection :*
12/28/2007 ELECTRIC - FINAL N/A Not ready for Inspection IVRS - Inspection :*

Completed Inspections

Permit Status: Expired
Permit Number: T07EL02231
Permit Description: ELECTRIC:REPAIR & REPLACE 100A SERVICE LIKE FOR LIKE
Total Completed Inspections - 3
Date Description Inspector Results Comments
12/28/2007 ELECTRIC - INTERMEDIATE RJIROUDE Approved 1. REVISE PERMIT TO SERVICE UPGRADE
2. SERVICE MAST TO BE MIN. 2"
3. INSTALL GROUND RODS
4. BOND GAS & WATER PIPING
5. INSTALL PROTECTIVE BUSHING WHERE ROMEX ENTERS EMT
01/04/2008 ELECTRIC - UNDERGROUND RJIROUDE Approved IVRS - Inspection :*
01/04/2008 TEP CLEARANCE - PM JWEATHER Approved INCR CLEARED PER R. JIROUDEK

Documents

File Name Document Type  
None DOCUMENTS VIEW