Permit: T07EL02231

Parcel: 131100790


Addresses:

5618 E 24TH ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/04/2008 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) WHEN USING METAL RACEWAY TO RUN GROUNDING ELECTRODE CONDUCTOR THE METAL RACEWAY NEEDS TO BE BONDED TO CONDUCTOR AT BOTH ENDS. METAL RACEWAY CAN BE REMOVED AND PANEL USED OR SECURE CONDUCTOR DIRECTLY TO BLDG SURFACE
12/28/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*