Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T07EL02209
Permit Details
Apply Date:
12/21/2007
Applicant:
ALPHA ONE ELECTRIC L L C * C
Description:
UPGRADE:ELECTRIC 100AMP TO 200AMP
Contractors:
- ALPHA ONE ELECTRIC L L C * C
Outstanding Activity Conditions
Permit Number - T07EL02209
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/21/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07EL02209
Permite Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/29/2008 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
| 02/29/2008 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT #4 COPPER ACROSS ROOF 2. SUPPORT NEW BOX & CAR FLEX ON ROOF DATE STAMPED 10/3/07 3. IDENTIFY CIRCUITS IN JUNCTION BOX TO VERIFY SHARED NEUTRALS 4. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 5. CLEAN PAINT UNDER LUG 250.12 6. TIGHTEN LOOSE FITTINGS 7. CAR FLEX SUPPORT TO BE WITHIN 12" OF BOX 8. SECURE NM CABLE TO BOX 312.5(C) 9. FINISH PREVIOUS ITEMS 7, 8, 10 & 13 |