Permit: T07EL02209

Parcel: 121021950


Addresses:

5528 E LINDEN ST


Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL02209

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
02/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT #4 COPPER ACROSS ROOF
2. SUPPORT NEW BOX & CAR FLEX ON ROOF DATE
STAMPED 10/3/07
3. IDENTIFY CIRCUITS IN JUNCTION BOX TO VERIFY SHARED NEUTRALS
4. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS
5. CLEAN PAINT UNDER LUG 250.12
6. TIGHTEN LOOSE FITTINGS
7. CAR FLEX SUPPORT TO BE WITHIN 12" OF BOX
8. SECURE NM CABLE TO BOX 312.5(C)
9. FINISH PREVIOUS ITEMS 7, 8, 10 & 13
02/22/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COMPLETELY DRIVE GROUND RODS
2. INSTALL LISTED MAST BRACING
3. ONE NEUTRAL PER TERMINAL ON NEUTRAL BAR
4. GROUND LUG NOT LISTED FOR 2 #4 TERMINATION
5. PROVIDE LADDER FOR INSPECTION
6. INSTALL BONDING BUSHING AT REDUCING WASHERS
7. CANNOT USE YELLOW WIRES FOR NEUTRAL
NEUTRAL #6 AND SMALLER TO BE IDENTIFIED ALONG ENTIRE LENGTH
8. GROUND BELL BOX
9. INSTALL PROPER COVER ON GFI RECEPTACLE
10. INSTALL CONNECTOR ON ROMEX ENTERING
BACK OF BELL BOX
11. CANNOT VERIFY GAS & WATER BOND
12. MAKE NEUTRAL CLOSER TO WEATHER HEAD
13. NEED DETAILED PANEL SCHEDULE NOT JUST GEN. LIGHTS AND RECEPTS.
14. SERVICE ENERGIZED PRIOR TO APPROVALS