Permit: T07EL02201
Permit Details
Apply Date:
12/20/2007
Applicant:
PALO VERDE ELECTRIC INC ,
Description:
UPGRADE:ELECTRIC 100AMP TO 200AMP
Contractors:
- PALO VERDE ELECTRIC INC ,
Outstanding Activity Conditions
Permit Number - T07EL02201
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/20/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T07EL02201
Permit Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/24/2007 | ELECTRIC - SERVICE UPGRADE | RHOLLAND | Approved | IVRS - Inspection :* 1) EXPOSED NM CABLE 2) CORDS NOT ALLOWED AS PERMANENT WIRING 400.7 3) MARKING TAPE TO ENCIRCLE CONDUCTOR 4) PROPERLY LABEL CIRCUIT BREAKERS PER 405.4-EXISTING IS NOT A CIRCUIT LABEL 5) GROUND RODS TO BE MINIMUM 6' APART 6) PLEASE VERIFY PERMIT FOR NEW A/C 7) SECURE NM CABLE TO JUNCTION BOX 8) SERVICE IS ENERGIZED WITHOUT CLEARANCE |
| 12/24/2007 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection :* |
| 01/22/2008 | PERMIT FINALED | JWEATHER | Approved | |
| 01/22/2008 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER R. HOLLANDER |