Permit: T07EL02167
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
4327 E EASTLAND ST
Address NEW:
4327 E EASTLAND ST
Apply Date:
12/12/2007
Applicant:
ENERGY SOURCE ELECTRIC INC *C
Description:
UPGRADE:ELECTRIC 100AMP TO 200AMP
Contractors:
- ENERGY SOURCE ELECTRIC INC *C
Outstanding Activity Conditions
Permit Number - T07EL02167
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/12/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07EL02167
Permite Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| ELECTRIC - SERVICE UPGRADE | N/A | Not Inspected | ||
| 12/20/2007 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND RODS TO BE MIN. 6' APART 2. VERIFY PERMIT FOR NEW AC EQUIPMENT. PROVIDE COPY OF PERMIT 3. PROVIDE DETAILED PANEL SCHEDULE/DIRECTORY 4. USE APPROVED FITTING FOR CONNECTION OF LB TO PANEL IF USING CHASE NIPPLE USE LOCKNUT ON OTHER SIDE 5. NEUTRAL CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ENTIRE LENGTH 6. CANNOT SEE INTO METER SECTION. SERVICE ENERGIZED PRIOR TO APPROVAL 7. HAVE #14 ON 20 AMP. CIRCUIT |
Completed Inspections
Permit Status: Expired
Permit Number: T07EL02167
Permit Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/14/2008 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER R. JIROUDEK |