Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
4327 E EASTLAND ST
Apply Date:
12/12/2007
Applicant:
ENERGY SOURCE ELECTRIC INC *C
Description:
UPGRADE:ELECTRIC 100AMP TO 200AMP
Contractors:
  • ENERGY SOURCE ELECTRIC INC *C

Outstanding Activity Conditions

Permit Number - T07EL02167
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Total Outstanding Activity Conditions - 1
Date Name
12/12/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07EL02167
Permite Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
ELECTRIC - SERVICE UPGRADE N/A Not Inspected
12/20/2007 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUND RODS TO BE MIN. 6' APART
2. VERIFY PERMIT FOR NEW AC EQUIPMENT.
PROVIDE COPY OF PERMIT
3. PROVIDE DETAILED PANEL SCHEDULE/DIRECTORY
4. USE APPROVED FITTING FOR CONNECTION OF LB TO PANEL IF USING CHASE NIPPLE USE LOCKNUT ON OTHER SIDE
5. NEUTRAL CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ENTIRE LENGTH
6. CANNOT SEE INTO METER SECTION. SERVICE ENERGIZED PRIOR TO APPROVAL
7. HAVE #14 ON 20 AMP. CIRCUIT

Completed Inspections

Permit Status: Expired
Permit Number: T07EL02167
Permit Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Total Completed Inspections - 1
Date Description Inspector Results Comments
01/14/2008 TEP CLEARANCE - AM JWEATHER Approved INCR CLEARED PER R. JIROUDEK

Documents

File Name Document Type  
None DOCUMENTS VIEW