Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) COMPLETE ITEM #7 FROM INSPECTION ON 12/20/07. HAVE #12 GOING TO SWITCH UNDER PANEL AND #14 GOING OUT. THIS IS SUPPLIED BY 20 AMP BREAKER. DO NOT HAVE PROPER SIZE GROUND FOR THIS CIRCUIT 2) CHECK PANEL DIRECTORY IT IS NOT ACCURATE |
|
| 01/08/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETE ITEM #2, #7 FROM INSPECTION ON 12/20/07 2. IDENTIFY NEUTRAL CONDUCTOR WITH RANGE CIRCUIT IF 3 WIRE CABLE 3RD CONDUCTOR IS NEUTRAL NOT EQUIPMENT GROUND. |
|
| 12/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND RODS TO BE MIN. 6' APART 2. VERIFY PERMIT FOR NEW AC EQUIPMENT. PROVIDE COPY OF PERMIT 3. PROVIDE DETAILED PANEL SCHEDULE/DIRECTORY 4. USE APPROVED FITTING FOR CONNECTION OF LB TO PANEL IF USING CHASE NIPPLE USE LOCKNUT ON OTHER SIDE 5. NEUTRAL CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ENTIRE LENGTH 6. CANNOT SEE INTO METER SECTION. SERVICE ENERGIZED PRIOR TO APPROVAL 7. HAVE #14 ON 20 AMP. CIRCUIT |