Date Description Inspector Results Comments
01/11/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) COMPLETE ITEM #7 FROM INSPECTION ON 12/20/07. HAVE #12 GOING TO SWITCH UNDER PANEL AND #14 GOING OUT. THIS IS SUPPLIED BY 20 AMP BREAKER. DO NOT HAVE PROPER SIZE GROUND FOR THIS CIRCUIT
2) CHECK PANEL DIRECTORY IT IS NOT ACCURATE
01/08/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COMPLETE ITEM #2, #7 FROM INSPECTION ON 12/20/07
2. IDENTIFY NEUTRAL CONDUCTOR WITH RANGE CIRCUIT
IF 3 WIRE CABLE 3RD CONDUCTOR IS NEUTRAL NOT EQUIPMENT GROUND.
12/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUND RODS TO BE MIN. 6' APART
2. VERIFY PERMIT FOR NEW AC EQUIPMENT.
PROVIDE COPY OF PERMIT
3. PROVIDE DETAILED PANEL SCHEDULE/DIRECTORY
4. USE APPROVED FITTING FOR CONNECTION OF LB TO PANEL IF USING CHASE NIPPLE USE LOCKNUT ON OTHER SIDE
5. NEUTRAL CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ENTIRE LENGTH
6. CANNOT SEE INTO METER SECTION. SERVICE ENERGIZED PRIOR TO APPROVAL
7. HAVE #14 ON 20 AMP. CIRCUIT