Permit: T07EL02135
Permit Details
Status:
Closed
Type:
SINGLE FAMILY OTHER
Address:
3320 E PATRICIA ST
Address NEW:
3320 E PATRICIA ST
Apply Date:
12/07/2007
Applicant:
JAMES R HERTZ
Description:
UPGRADE:ELECTRIC 200AMP
Outstanding Activity Conditions
Permit Number - T07EL02135
Permit Status: Closed
Permit Description: UPGRADE:ELECTRIC 200AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/07/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Closed
Permit Number: T07EL02135
Permite Description: UPGRADE:ELECTRIC 200AMP
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/28/2008 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL ROOF JACK AT MAST PENETRATION THROUGH ROOF 2. SERVICE CONDUCTORS NOT SIZED PROPERLY FOR 200 AMP SERVICE 3. INSTALL CONNECTOR ON SERVICE CABLE ENTERING BACK OF 2 GANG BELL BOX 4. SECURE CONDUCTORS TO BUILDING SURFACE UNDER PANEL 5. CANNOT USE EMT FOR MAST BRACING USE LISTED KIT 6. THIS INSPECTOR HAS WITNESSED NEW WORK INSIDE HOME THAT REQUIRE PLANS & PERMIT. POWER WILL NOT BE RELEASED UNTIL THIS IS ACCOMPLISHED. PLEASE VERIFY PERMITS. |