Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Closed
Type:
SINGLE FAMILY OTHER
Address NEW:
3320 E PATRICIA ST
Apply Date:
12/07/2007
Applicant:
JAMES R HERTZ
Description:
UPGRADE:ELECTRIC 200AMP

Outstanding Activity Conditions

Permit Number - T07EL02135
Permit Status: Closed
Permit Description: UPGRADE:ELECTRIC 200AMP
Total Outstanding Activity Conditions - 1
Date Name
12/07/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Closed
Permit Number: T07EL02135
Permite Description: UPGRADE:ELECTRIC 200AMP
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
01/28/2008 ELECTRIC - SERVICE UPGRADE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL ROOF JACK AT MAST PENETRATION
THROUGH ROOF
2. SERVICE CONDUCTORS NOT SIZED PROPERLY
FOR 200 AMP SERVICE
3. INSTALL CONNECTOR ON SERVICE CABLE ENTERING BACK OF 2 GANG BELL BOX
4. SECURE CONDUCTORS TO BUILDING SURFACE UNDER PANEL
5. CANNOT USE EMT FOR MAST BRACING USE LISTED KIT
6. THIS INSPECTOR HAS WITNESSED NEW WORK INSIDE HOME THAT REQUIRE PLANS & PERMIT. POWER WILL NOT BE RELEASED UNTIL THIS IS ACCOMPLISHED. PLEASE VERIFY PERMITS.

Documents

File Name Document Type  
None DOCUMENTS VIEW