Permit: T07EL02135

Parcel: 111063000


Addresses:

3320 E PATRICIA ST

Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/28/2008 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL ROOF JACK AT MAST PENETRATION
THROUGH ROOF
2. SERVICE CONDUCTORS NOT SIZED PROPERLY
FOR 200 AMP SERVICE
3. INSTALL CONNECTOR ON SERVICE CABLE ENTERING BACK OF 2 GANG BELL BOX
4. SECURE CONDUCTORS TO BUILDING SURFACE UNDER PANEL
5. CANNOT USE EMT FOR MAST BRACING USE LISTED KIT
6. THIS INSPECTOR HAS WITNESSED NEW WORK INSIDE HOME THAT REQUIRE PLANS & PERMIT. POWER WILL NOT BE RELEASED UNTIL THIS IS ACCOMPLISHED. PLEASE VERIFY PERMITS.
01/16/2008 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NO SERVICE CONDUCTORS INSTALLED
2. GROUND RODS TO BE MIN. 6' APART
3. INSTALL ROOF JACK
4. PROVIDE LADDER FOR INSPECTION
5. HAVE WEATHERHEAD FACE DIRECTION OF SERVICE DROP CONDUCTORS
6. LUG NOT LISTED FOR 2-WIRE TERMINATION IN PANEL
7. VERIFY IF POWER HAS BEEN OFF FOR MORE THAN 6 MONTHS WILL NEED TO HAVE RECONNECT INSPECTION ADDED TO ACTIVITY. INSPECTOR WILL NEED ACCESS TO INTERIOR OF UNIT.
8. NEED 3' CLEARANCE FROM ELECTRIC PANEL TO REGULATOR VENT ON GAS METER
9. INSTALL BREAKERS LISTED FOR USE IN SQUARE D PANEL