Permit: T07EL02101
Permit Details
Apply Date:
12/03/2007
Applicant:
GLOVER SR.
Description:
UPGRADE:ELECTRIC 100AMP TO 200AMP:CIR FOR SPA
Contractors:
- GLOVER SR.
Permit Reviews
Permit Number - T07EL02101
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 100AMP TO 200AMP:CIR FOR SPA
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 12/03/2007 | ELECTRICAL | 12/03/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T07EL02101
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 100AMP TO 200AMP:CIR FOR SPA
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/03/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07EL02101
Permite Description: UPGRADE:ELECTRIC 100AMP TO 200AMP:CIR FOR SPA
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/28/2007 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
| 12/28/2007 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROPERLY INSTALL GROUND CLAMP AT WATER CONNECTION 2. TIGHTEN ACORN GROUND ROD CLAMP 3. SECURE OR BURY GROUNDING ELECTRODE CONDUCTOR 4. USE APPROVED STRAPPING METHODS 5. PLEASE VERIFY CLEARANCES PER 680.10 6. FULLY INSTALL FITTINGS AT JUNCTION BOX 7. MAINTAIN WORKING CLEARANCES 110.26 SPA DISCONNECT 8. NEED TO SEE SPA CONNECTIONS |