Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/11/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* SPA: 1. TIGHTEN LOOSE FITTINGS AND SUPPORT AND PROTECT LFNC 2. NEED TO SEE CONNECTION TO INSIDE OF SPA 3. INSTALL ALL STRANDS UNDER TERMINAL LUG FINISH PREVIOUS ITEMS 2, 3, 5, 6 AND 8 (12/28/07 INSP.) PLEASE VERIFY QUALIFIED ELECTRICIAN DOING WORK |
|
| 12/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROPERLY INSTALL GROUND CLAMP AT WATER CONNECTION 2. TIGHTEN ACORN GROUND ROD CLAMP 3. SECURE OR BURY GROUNDING ELECTRODE CONDUCTOR 4. USE APPROVED STRAPPING METHODS 5. PLEASE VERIFY CLEARANCES PER 680.10 6. FULLY INSTALL FITTINGS AT JUNCTION BOX 7. MAINTAIN WORKING CLEARANCES 110.26 SPA DISCONNECT 8. NEED TO SEE SPA CONNECTIONS |
|
| 12/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PANEL LABELING TO BE AS PER 408.4 - LEGIBLE - ABBREVIATIONS 2. FILL UNUSED OPENINGS IN BACK OF PANEL 3. USE APPROVED FITTINGS WITH LB 4. BOND TO INTERIOR WATER PIPING AROUND SOFT WATER SOFTENER ALSO BOND GAS 5. USE APPROVED STRAP FOR RISER AND 1/4" MIN. HARDWARE 6. A LISTED MAST BRACE KIT IS NEEDED 7. MAINTAIN CLEARANCES FROM POOL WATER PER 680.10 8. PLEASE IDENTIFY NEUTRAL CLOSER TO WEATHERHEAD 9. SUPPORT CONDUIT BELOW PANEL AND PROTECT CABLE FROM SHARP METAL EDGES. *NOTE: WILL NEED TO SEE SPA CONNECTIONS. |