Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
DUPLEX OTHER
Address NEW:
2103 S CAMPBELL AV
Apply Date:
11/13/2007
Applicant:
CHRISTOPHER JAMES EDWARD
Description:
UPGRADE: 100 AMP DUPLEX

Permit Reviews

Permit Number - T07EL02016
Permit Status: Final
Permit Description: UPGRADE: 100 AMP DUPLEX
Start Date Submittal Complete Date Status  
11/13/2007 ELECTRICAL 11/13/2007 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T07EL02016
Permit Status: Final
Permit Description: UPGRADE: 100 AMP DUPLEX
Total Outstanding Activity Conditions - 1
Date Name
11/13/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T07EL02016
Permit Description: UPGRADE: 100 AMP DUPLEX
Total Completed Inspections - 3
Date Description Inspector Results Comments
12/10/2007 ELECTRIC - SERVICE UPGRADE DSANTACR Approved IVRS - Inspection :
See detailed listing on site.| 999*
1. SUPPORT #6 GROUNDING ELECTRODE CONDUCTOR TO WALL, USE APPROVED STRAPS. ALSO #4
2. USE SPLIT BOLT TO TAP ONE GROUND ELECTRODE CONDUCTOR TO THE OTHER
3. USE PROPER CLAMP FOR #6 AT SECOND GROUND ROD, ONE CONDUCTOR PER ACORN CLAMP
4. USE SIEMENS BREAKER IN SUB-PANEL AS PER MANUF. LISTING
5. TIGHTEN LOOSE FITTINGS
6. #14 GAUGE WIRE SHOULD BE ON 15 AMP BREAKER
7. FILL IN OPENINGS BEHIND PANELS WITH FIREPROOF SEALANT
8. OUTSIDE RECEPT, NEEDS TO BE GFI PROTECTED
9. INSTALL PERMANENT ADDRESS LABELS ON SERVICE PANELS
10. LABEL CIRCUIT BREAKERS
11. BOND WATER & GAS PIPING
01/11/2008 TEP CLEARANCE - PM JWEATHER Approved INCR CLEARED FOR 2103 & 2105 S. CAMPBELL AVE PER D. SANTACRUZ
07/08/2008 PERMIT FINALED LJACKSON Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW