Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 12/10/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT #6 GROUNDING ELECTRODE CONDUCTOR TO WALL, USE APPROVED STRAPS. ALSO #4 2. USE SPLIT BOLT TO TAP ONE GROUND ELECTRODE CONDUCTOR TO THE OTHER 3. USE PROPER CLAMP FOR #6 AT SECOND GROUND ROD, ONE CONDUCTOR PER ACORN CLAMP 4. USE SIEMENS BREAKER IN SUB-PANEL AS PER MANUF. LISTING 5. TIGHTEN LOOSE FITTINGS 6. #14 GAUGE WIRE SHOULD BE ON 15 AMP BREAKER 7. FILL IN OPENINGS BEHIND PANELS WITH FIREPROOF SEALANT 8. OUTSIDE RECEPT, NEEDS TO BE GFI PROTECTED 9. INSTALL PERMANENT ADDRESS LABELS ON SERVICE PANELS 10. LABEL CIRCUIT BREAKERS 11. BOND WATER & GAS PIPING |