Permit: T07EL02016

Parcel: 130051610


Addresses:

2103 S CAMPBELL AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/10/2008 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
12/10/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SUPPORT #6 GROUNDING ELECTRODE CONDUCTOR TO WALL, USE APPROVED STRAPS. ALSO #4
2. USE SPLIT BOLT TO TAP ONE GROUND ELECTRODE CONDUCTOR TO THE OTHER
3. USE PROPER CLAMP FOR #6 AT SECOND GROUND ROD, ONE CONDUCTOR PER ACORN CLAMP
4. USE SIEMENS BREAKER IN SUB-PANEL AS PER MANUF. LISTING
5. TIGHTEN LOOSE FITTINGS
6. #14 GAUGE WIRE SHOULD BE ON 15 AMP BREAKER
7. FILL IN OPENINGS BEHIND PANELS WITH FIREPROOF SEALANT
8. OUTSIDE RECEPT, NEEDS TO BE GFI PROTECTED
9. INSTALL PERMANENT ADDRESS LABELS ON SERVICE PANELS
10. LABEL CIRCUIT BREAKERS
11. BOND WATER & GAS PIPING