Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address NEW:
488 N ALVERNON WY
Apply Date:
11/08/2007
Applicant:
RICHARD W SERCER
Description:
RECONNECT:ELECTRIC:OFFICE

Outstanding Activity Conditions

Permit Number - T07EL01993
Permit Status: Expired
Permit Description: RECONNECT:ELECTRIC:OFFICE
Total Outstanding Activity Conditions - 1
Date Name
11/08/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07EL01993
Permite Description: RECONNECT:ELECTRIC:OFFICE
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
11/09/2007 ELECTRIC - RECONNECT N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL CORRECT ADDRESS FOR SPACE TO MATCH PERMIT
2. SERVICE HAS SEVERAL SAFETY CONCERNS - PARTIAL INSPECTION REVEALS SERVICE DROP TO LOW WITH BARE CONDUCTORS, SERVICE EQUIPMENT NOT RAIN TIGHT AND IS DETERIORATED AND CORRODED, EQUIPMENT IS NOT IDENTIFIED GROUNDING & BONDING CONDUCTORS HAVE BEEN STOLEN. SERVICE IS IMPROPERLY WIRED ETC. STRONGLY RECOMMENDED UPGRADE OF SERVICE TO MEET CURRENT CODE.
3. REPLACE PAINTED OVER DEVICES, INSTALL ALL COVERS
TIGHTEN LOOSE DEVICES. 3-WAY SWITCH REAR EXIT NOT WORKING.

PARTIAL LIST

Completed Inspections

Permit Status: Expired
Permit Number: T07EL01993
Permit Description: RECONNECT:ELECTRIC:OFFICE
Total Completed Inspections - 1
Date Description Inspector Results Comments
11/09/2007 FIRE - FINAL LTHOMAS Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW