Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2007 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL CORRECT ADDRESS FOR SPACE TO MATCH PERMIT 2. SERVICE HAS SEVERAL SAFETY CONCERNS - PARTIAL INSPECTION REVEALS SERVICE DROP TO LOW WITH BARE CONDUCTORS, SERVICE EQUIPMENT NOT RAIN TIGHT AND IS DETERIORATED AND CORRODED, EQUIPMENT IS NOT IDENTIFIED GROUNDING & BONDING CONDUCTORS HAVE BEEN STOLEN. SERVICE IS IMPROPERLY WIRED ETC. STRONGLY RECOMMENDED UPGRADE OF SERVICE TO MEET CURRENT CODE. 3. REPLACE PAINTED OVER DEVICES, INSTALL ALL COVERS TIGHTEN LOOSE DEVICES. 3-WAY SWITCH REAR EXIT NOT WORKING. PARTIAL LIST |