Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
315 S STEFAN PL
Address NEW:
315 S STEFAN PL
Apply Date:
11/06/2007
Applicant:
MEHL SANDRA
Description:
Replace existing meter base and panel, like for like, 200amp all in one.
Contractors:
  • MEHL ELECTRIC SERVICE INC,*C

Outstanding Activity Conditions

Permit Number - T07EL01966
Permit Status: Expired
Permit Description: Replace existing meter base and panel, like for like, 200amp all in one.
Total Outstanding Activity Conditions - 1
Date Name
11/06/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07EL01966
Permite Description: Replace existing meter base and panel, like for like, 200amp all in one.
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
12/14/2007 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUNDING CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ALONG ENTIRE LENGTH. GREEN/BARE COPPER
2. ALUMINUM & COPPER CONDUCTORS CANNOT BE SPLICED TOGETHER
3. CHECK SPLICES IN JUNCTION BOX HAVE COPPER SHOWING OUT BOTTOM OF WIRE NUTS.

Completed Inspections

Permit Status: Expired
Permit Number: T07EL01966
Permit Description: Replace existing meter base and panel, like for like, 200amp all in one.
Total Completed Inspections - 1
Date Description Inspector Results Comments
11/29/2007 TEP CLEARANCE - AM JWEATHER Approved INCR CLEARED PER R. JIROUDEK

Documents

File Name Document Type  
None DOCUMENTS VIEW