Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/14/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUNDING CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ALONG ENTIRE LENGTH. GREEN/BARE COPPER
2. ALUMINUM & COPPER CONDUCTORS CANNOT BE SPLICED TOGETHER
3. CHECK SPLICES IN JUNCTION BOX HAVE COPPER SHOWING OUT BOTTOM OF WIRE NUTS.
11/28/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NEED TO DERATE AMPICITY OF CONDUCTORS IN REACEWAYS. HAVE MORE THAN 3 CURRENT CARRYING CONDUCTORS IN EACH RACEWAY
2) INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL
3) ALL CONDUCTORS FOR CIRCUITS NEED TO BE RUN IN SAME RACEWAY. HOTS, NEUTRAL AND GROUND
4) OK GROUND RODS, WATER AND GAS BOND
5) RECALL WHEN ALL WORK COMPLETE. THIS IS NOT A COMPLETE LIST
6) CALLED TEP MAP ROOM AND GAVE CLEARANCE