Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T07EL01938
Permit Details
Apply Date:
11/01/2007
Applicant:
HAMSTRA HEATING AND COOLING INC,*C
Description:
UPGRADE: 125 AMP DUPLEX (APA)
Contractors:
- HAMSTRA HEATING AND COOLING INC,*C
Outstanding Activity Conditions
Permit Number - T07EL01938
Permit Status: Final
Permit Description: UPGRADE: 125 AMP DUPLEX (APA)
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
11/01/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T07EL01938
Permit Description: UPGRADE: 125 AMP DUPLEX (APA)
Total Completed Inspections - 4
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/12/2007 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection :* 1. USE APPROVED FITTING WITH LB AND BOND AT SERVICE 2. ONLY ONE CONDUCTOR PER TERMINAL LUG 3. MAINTAIN WORKING CLEARANCE 4. ATTACH GROUNDS TO STRUCTURE 5. REPLACE CONDUCTOR WITH TAPE WITH INSULATED GROUNDED CONDUCTOR 6. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS 7. CLOSE JUNCTION BOX IN BASEMENT 8. A PERMIT IS NEEDED FOR NEW AC UNITS |
12/12/2007 | ELECTRIC - SERVICE UPGRADE | RHOLLAND | Approved | IVRS - Inspection :* |
01/24/2008 | PERMIT FINALED | JWEATHER | Approved | |
01/24/2008 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED FOR 601 & 603 E. 2ND ST PER R. HOLLANDER |