Permit: T07EL01938

Parcel: 117022980


Addresses:

601 E 2ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL01938

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/23/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/15/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
PLANS TO BE ON SITE
12/12/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. USE APPROVED FITTING WITH LB AND BOND AT SERVICE
2. ONLY ONE CONDUCTOR PER TERMINAL LUG
3. MAINTAIN WORKING CLEARANCE
4. ATTACH GROUNDS TO STRUCTURE
5. REPLACE CONDUCTOR WITH TAPE WITH INSULATED GROUNDED CONDUCTOR
6. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS
7. CLOSE JUNCTION BOX IN BASEMENT
8. A PERMIT IS NEEDED FOR NEW AC UNITS
11/07/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
ROOF: NO MORE THAN 360 DEG. IN A CONDUIT RUN

1. FINISH PREVIOUS ITEMS
2. PLEASE VERIFY PERMIT FOR NEW ROOF AC UNITS
11/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. MAINTAIN WORKING CLEARANCES IN FRONT OF
SERVICE 110.26
2. VERIFY NEW GROUNDING ELECTRODE SYSTEM & GAS & WATER BONDS
3. PROTECT CONDUCTORS 300.4
4. FITTING TO BE LISTED FOR BONDING
5. PANED SCHEDULES TO BE AS PER 408.4 - NO GENERAL LABELING OR ABBREVIATIONS
6. SEAL ENTRANCES ABOVE CURENT CARRING PARTS WITH APPROVED DEVICES
7. VERIFY INTERIOR CIRCUIT AMPACITIES
8. USE LISTED & APPROVED FITTINGS FOR WET LOCATION
9. SUPPORT CONDUITS AS PER CODE
10. TIGHTEN FITTINGS
11. PROVIDE ROOF ACCESS TO INSPECT CONDUIT & JUNCTION BOXES